Float-Operated Level Control Condensate Pump
The Liqui-Mover float level control is 100% mechanical - it requires no electricity to operate. This makes it well suited to remote locations, like tank farms, where it is impractical to supply electricity.
Float-operated level control condensate pumps are also used where electricity can be hazardous. This includes wet environments like sumps/pits, bottle washers, laundry equipment, and explosive environments such as refineries, chemical plants or distillation towers.
Download case study to learn more on how a Liqui-Mover pump can prevent the loss of condensate and associated energy losses. (53K)
| Stage 1: Fill Stage | Stage 2: Pump Stage | Stage 3: Equalize Stage |
![]() |
![]() |
![]() |
| Fluid flows from the receiving chamber (A) through the inlet check valve (B) into the pump tank (C). The 3-way valve (D) is open between the pump tank and the receiving chamber, equalizing the pressure between them through the equalizing line (E). | When the level control (F) senses that the pump tank is full, the 3-way valve energizes to admit the motive pressure into the pump tank (C). The motive pressure forces the fluid past the discharge check valve (H) and out the discharge line. | Once the level control (F) senses the pump tank has emptied, the 3-way valve (D) de-energizes, shutting off the motive pressure, and opening the vent port in the valve. This allows the pump tank (C) and the receiving chamber (A) to equalize in pressure. The cycle will now repeat. |
| Model | Maximum Capacity* (pph) | Check Valve Size | PMA (psig) | TMA (°F) | Pump Body Material |
|---|---|---|---|---|---|
| LMHT-500 Low Profile Series |
2,830 | 1" x 1" | 200 | 400 | ASTM A395 Class 60 ductile iron ASME rated 200 psig |
| LMHT-1600 Low Profile Series |
4,060 | 1" x 1" | 150 | 450 | Fabricated Steel 150 psig ASME "U" stamped |
| 8,860 | 1-1/2" x 1-1/2" | ||||
| 12,490 | 2" x 2" | ||||
| 14,660 | 3" x 2" | ||||
| LMV-1600 Series | 3,690 | 1" x 1" | 150 | 450 | Fabricated steel 150 psig ASME "U" stamped |
| 7,770 | 1-1/2" 1-1/2" | ||||
| 10,910 | 2" x 2' | ||||
| 13,540 | 3" x 2" |
* Above Capacities are based on:
- Single pump tank
- Steam as motive pumping pressure
- Maximum fill head
- Motive pressure being 20 psig higher than static back pressure
- 210°F condensate temperature